Tri Rizki Prasetya, - (2018) PERANCANGAN KONTROL OTOMATIS PADA PANEL PERBAIKAN FAKTOR DAYA UNTUK MOTOR-MOTOR LISTRIK. D3 thesis, Universitas Pendidikan Indonesia.
Text
TA_TE_1505700_Title.pdf Download (59kB) |
|
Text
TA_TE_1505700_Tabel_of_Content.pdf Download (135kB) |
|
Text
TA_TE_1505700_Abstract.pdf Download (94kB) |
|
Text
TA_TE_1505700_Chapter1.pdf Download (116kB) |
|
Text
TA_TE_1505700_Chapter2.pdf Restricted to Staf Perpustakaan Download (501kB) |
|
Text
TA_TE_1505700_Chapter3.pdf Download (342kB) |
|
Text
TA_TE_1505700_Chapter4.pdf Restricted to Staf Perpustakaan Download (476kB) |
|
Text
TA_TE_1505700_Chapter5.pdf Download (110kB) |
|
Text
TA_TE_1505700_Bibliography.pdf Download (70kB) |
|
Text
TA_TE_1505700_Appendix1.pdf Restricted to Staf Perpustakaan Download (301kB) |
|
Text
TA_TE_1505700_Appendix2.pdf Restricted to Staf Perpustakaan Download (486kB) |
|
Text
TA_TE_1505700_Appendix3.pdf Restricted to Staf Perpustakaan Download (569kB) |
Abstract
In the industrial world, most of them use electric motors that have an influence on the electricity of PLN as a whole because electric motors have a power factor of less than one. Then we need a tool to improve the value of the power factor that is less than one, then the device is a bank capacitor. Likewise in a power electricity laboratory that has a lot of electric motors that need to be repaired its power factor value. In the design of the capacitor, the author's bank is only focused on controlling the improvement of the power factor so that the capacitor of the bank can work automatically. The design of the bank capacitor that is made needs to be analyzed using data collection methods and the design techniques of bank capacitors. The working method of the tool is that the device is provided with a 380 volt voltage source that flows through the com, P0 and P2 on the MH MSC-12 power factor controller so that it can function. After that the control can be set according to the desired needs. Some settings found on the MH MSC-12 power factor controller are delay, step, power factor and others. From the results of trials and measurements it can be concluded that the MH MSC-12 power factor controller can work in accordance with what has been set. Whenset to correctcos the electric motorwith a current of 3.6A which initially has a cos value of 0.60 to be 0.85 in accordance with what is desired, the regulator works well and can correct cos in accordance with the settings. So the cos motor turns to 0.86. Whensetting to correct cos electric motor which has a current of 4.8 A which is cos φ initially 0.71 so that it becomes 0.95 according to what is desired, the regulator works well and can correct cos according to the setting, so cos the motor changes to 0.95. With this tool it will reduce the occurrence of voltage drop, minimize the occurrence of electricity network losses, prevent PLN fines due to reactive power.
Item Type: | Thesis (D3) |
---|---|
Additional Information: | No. Panggil : TA TE TRI p-2018 ; Pembimbing I. I Wayan Ratnata, II. Tasma Sucita ; NIM : 1505700 |
Uncontrolled Keywords: | Power Capacitor, Power Factor, MH MSC-12 Power Factor Controller. |
Subjects: | Q Science > Q Science (General) Q Science > QA Mathematics > QA75 Electronic computers. Computer science T Technology > T Technology (General) |
Divisions: | Fakultas Pendidikan Teknologi dan Kejuruan > Jurusan Pendidikan Teknik Elektro > Program D3 Teknik Elektro |
Depositing User: | Mr Tatang Saja |