PERBANDINGAN EFISIENSI PEMBANGKITAN ENERGI LISTRIK PADA PLTA SAGULING SUB UNIT PLTA LAMAJAN DAN CIKALONG BERDASARKAN VARIABEL DEBIT AIR DAN KETINGGIAN (HEAD) AIR YANG JATUH

    Mohhamad Fahril Permadiana, - and Wasimudin Surya Saputra, - (2025) PERBANDINGAN EFISIENSI PEMBANGKITAN ENERGI LISTRIK PADA PLTA SAGULING SUB UNIT PLTA LAMAJAN DAN CIKALONG BERDASARKAN VARIABEL DEBIT AIR DAN KETINGGIAN (HEAD) AIR YANG JATUH. S1 thesis, Universitas Pendidikan Indonesia.

    Abstract

    Kebutuhan energi listrik di Indonesia terus meningkat, sementara potensi energi air melalui Pembangkit Listrik Tenaga Air (PLTA) belum dimanfaatkan secara optimal. Oleh karena itu efisiensi pembangkitan menjadi faktor penting untuk memastikan pasokan listrik yang andal dan berkelanjutan. Penelitian ini dilatarbelakangi oleh adanya perbedaan efisiensi antara PLTA Lamajan dan PLTA Cikalong, usia infrastruktur yang relatif tua (Lamajan 100 tahun; Cikalong 63 tahun), serta belum adanya kajian perbandingan efisiensi secara komprehensif. Penelitian ini bertujuan untuk menganalisis pengaruh debit dan ketinggian (head) air terhadap efisiensi daya, membandingkan efisiensi kedua PLTA, dan mengidentifikasi faktor-faktor yang memengaruhi kinerja pembangkit. Metode yang digunakan adalah kuantitatif dengan pendekatan komparatif deskriptif berdasarkan data operasional periode Juli hingga Desember 2024. Hasil penelitian menunjukkan bahwa debit dan head berpengaruh signifikan terhadap potensi serta produksi daya, namun tidak selalu berbanding lurus dengan efisiensi. PLTA Lamajan memiliki potensi daya 1,25 GW dan produksi 1,13 GW dengan efisiensi 90,03%, sedangkan PLTA Cikalong memiliki potensi 1,05 GW dan produksi 0,76 GW dengan efisiensi 72,16%. Perbedaan efisiensi ini dipengaruhi oleh kondisi komponen utama, usia peralatan, dan strategi operasional. Hal ini dibuktikan dengan perhitungan efisiensi generator selama periode Juli hingga Desember dalam kondisi minimal PLTA Lamajan memiliki kondisi yang lebih optimal, yaitu sebesar 97,86%, sedangkan PLTA Cikalong hanya sebesar 78,43%. Rekomendasi yang diberikan meliputi pengaturan debit pemakaian air secara presisi pada PLTA Lamajan dan evaluasi mendalam terhadap turbin serta generator pada PLTA Cikalong. Penelitian lanjutan disarankan mencakup periode data lebih panjang, analisis detail komponen pembangkit, dan pemanfaatan teknologi pemantauan berbasis IoT untuk optimasi kinerja. The demand for electricity in Indonesia continues to increase, while the potential of hydropower through Hydroelectric Power Plants (HPP) has not yet been optimally utilized. Therefore, generation efficiency becomes a crucial factor in ensuring a reliable and sustainable electricity supply. This research is motivated by the efficiency differences between Lamajan HPP and Cikalong HPP, the relatively old age of infrastructure (Lamajan 100 years; Cikalong 63 years), and the absence of a comprehensive efficiency comparison study. The objectives of this study are to analyze the effect of water discharge and head height on power efficiency, compare the efficiency of both HPPs, and identify factors influencing plant performance. The method used is quantitative with a descriptive comparative approach based on operational data from July to December 2024. The results show that discharge and head significantly affect power potential and production but are not always directly proportional to efficiency. Lamajan HPP has a power potential of 1.25 GW and production of 1.13 GW with an efficiency of 90.03%, while Cikalong HPP has a power potential of 1.05 GW and production of 0.76 GW with an efficiency of 72.16%. This efficiency difference is influenced by the condition of main components, equipment age, and operational strategies. This is evidenced by generator efficiency calculations during the July to December period, showing that Lamajan HPP operates in a more optimal condition at 97.86%, compared to Cikalong HPP at only 78.43%. Recommendations include precise regulation of water usage discharge at Lamajan HPP and in-depth evaluation of turbines and generators at Cikalong HPP. Further research is suggested to cover a longer data period, detailed analysis of plant components, and the application of IoT-based monitoring technology for performance optimization.

    [thumbnail of S_TE_2104452_Title.pdf] Text
    S_TE_2104452_Title.pdf

    Download (402kB)
    [thumbnail of S_TE_2104452_Chapter1.pdf] Text
    S_TE_2104452_Chapter1.pdf

    Download (265kB)
    [thumbnail of S_TE_2104452_Chapter2.pdf] Text
    S_TE_2104452_Chapter2.pdf
    Restricted to Staf Perpustakaan

    Download (1MB)
    [thumbnail of S_TE_2104452_Chapter3.pdf] Text
    S_TE_2104452_Chapter3.pdf

    Download (1MB)
    [thumbnail of S_TE_2104452_Chapter4.pdf] Text
    S_TE_2104452_Chapter4.pdf
    Restricted to Staf Perpustakaan

    Download (597kB)
    [thumbnail of S_TE_2104452_Chapter5.pdf] Text
    S_TE_2104452_Chapter5.pdf

    Download (259kB)
    [thumbnail of S_TE_2104452_Appendix.pdf] Text
    S_TE_2104452_Appendix.pdf
    Restricted to Staf Perpustakaan

    Download (677kB)
    Official URL: https://repository.upi.edu
    Item Type: Thesis (S1)
    Additional Information: https://scholar.google.com/citations?view_op=new_profile&hl=en ID SINTA Dosen Pembimbing: Wasimudin Surya Saputra: 5978996
    Uncontrolled Keywords: PLTA Lamajan, PLTA Cikalong, Efisiensi Pembangkitan, Debit Air, Ketinggian air, Perbandingan Kinerja. Lamajan HPP, Cikalong HPP, Generation Efficiency, Water Discharge, Head Height, Performance Comparison.
    Subjects: Q Science > QA Mathematics
    Q Science > QC Physics
    T Technology > TK Electrical engineering. Electronics Nuclear engineering
    Divisions: Fakultas Pendidikan Teknik dan Industri > Jurusan Pendidikan Teknik Elektro > Program Studi Teknik Tenaga Elektrik
    Depositing User: Mohhamad Fahril Permadiana
    Date Deposited: 07 Nov 2025 06:40
    Last Modified: 07 Nov 2025 06:40
    URI: http://repository.upi.edu/id/eprint/144921

    Actions (login required)

    View Item View Item