<> "The repository administrator has not yet configured an RDF license."^^ . <> . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT"^^ . "Circuit Breaker (CB) atau Pemutus Tenaga (PMT) adalah sakelar mekanis yang berfungsi \r\nuntuk mengalirkan dan memutus arus beban, baik dalam kondisi normal atau abnormal \r\nseperti gangguan hubung singkat. Kerusakan pada Pemutus Tenaga (PMT) berdampak \r\nsignifikan pada operasional sistem tenaga listrik, menyebabkan kerugian dan kerusakan \r\nlebih lanjut. Oleh karena itu, pengujian kelayakan Pemutus Tenaga (PMT) secara rutin \r\ndiperlukan untuk memastikan kesesuaian standar, meningkatkan keandalan, dan menjaga \r\nkontinuitas penyaluran tenaga listrik. Tujuan dari penelitian ini untuk menilai kelayakan \r\nPemutus Tenaga (PMT) 20 kV dengan menggunakan hasil uji tahanan isolasi, tahanan \r\nkontak dan keserempakan kontak. Metode pengumpulan data meliputi studi literatur, \r\ndiskusi, dan observasi langsung pada Pemutus Tenaga (PMT) penyulang RKU di Gardu \r\nInduk Rancaekek PT PLN (Persero) UP2D Jawa Barat. Hasil pengujian menunjukan bahwa \r\ntahanan isolasi terendah pada titik ukur bawah-tanah phasa S sebesar 0,886 TΩ dengan arus \r\nbocor sebesar 0,0135 mA, nilai ini memenuhi standar minimum tahanan isolasi yang \r\nbekerja pada tegangan 20 kV sebesar 0,0833 TΩ. Sedangkan hasil pengujian tahanan \r\nkontak pada masing-masing phasa masih berada di bawah 50 µΩ, dengan nilai terendah \r\npada phasa R 30,9 µΩ dengan rugi daya sebesar 0,309 W. Pada keserempakan kontak, hasil \r\nperhitungan selisih waktu pada posisi close dan open berada di bawah 10 ms dengan nilai \r\nclose sebesar 0,8 ms dan open 0,2 ms. Dengan demikian pemutus tenaga (PMT) 20 kV \r\npada penyulang RKU dalam kondisi aman dan layak untuk dioperasikan sesuai dengan \r\nstandar. Penelitian ini diharapkan dapat menambah pemahaman tentang pentingnya \r\npemeliharaan preventif pada peralatan listrik khususnya Pemutus Tenaga (PMT) untuk \r\nmenjaga keandalan distribusi tenaga listrik. \r\n\r\nCircuit Breaker (CB) or Power Breaker (PMT) is a mechanical switch that functions to \r\nflow and break the load current, both in normal or abnormal conditions such as short \r\ncircuit faults. Damage to the Power Breaker (PMT) has a significant impact on the \r\noperation of the electric power system, causing further losses and damage. Therefore, \r\nroutine testing of the feasibility of the Power Breaker (PMT) is needed to ensure compliance \r\nwith standards, improve reliability, and maintain continuity of electric power distribution. \r\nThe purpose of this study is to assess the feasibility of the 20 kV Power Breaker (PMT) \r\nusing the results of insulation resistance, contact resistance and contact simultaneity tests. \r\nData collection methods include, literature studies, discussion and direct observation of \r\nthe Power Breaker (PMT) feeder RKU at the Rancaekek Substation of PT PLN (Persero) \r\nUP2D West Java. The test results show that the lowest insulation resistance at the S phase \r\nunderground measuring point is 0.886 TΩ with a leakage current of 0.0135 mA, this value \r\nmeets the minimum standard for insulation resistance working at a voltage of 20 kV of \r\n0.0833 TΩ. While the results of the contact resistance test on each phase are still below 50 \r\nµΩ, with the lowest value on the R phase of 30.9 µΩ with a power loss of 0.309 W. At the \r\nsimultaneity of contact, the calculation results of the time difference in the close and open \r\npositions are below 10 ms with a close value of 0.7 ms and an open value of 0.2 ms. Thus, \r\nthe 20 kV circuit breaker (PMT) on the RKU feeder is in a safe condition and is suitable \r\nfor operation according to standards. This study is expected to increase understanding of \r\nthe importance of preventive maintenance on electrical equipment, especially Circuit \r\nBreakers (PMT) to maintain the reliability of electric power distribution."^^ . "2025-01-24" . . . . . . . . . "Universitas Pendidikan Indonesia"^^ . . . "KODEPRODI83201#Pendidikan_Teknik_Elektro_S1, Universitas Pendidikan Indonesia"^^ . . . . . . . . . . . . . "-"^^ . "Seli Sanustika"^^ . "- Seli Sanustika"^^ . . "-"^^ . "Tasma Sucita"^^ . "- Tasma Sucita"^^ . . . . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . . "S_TE_2108888_Title.pdf"^^ . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . . "S_TE_2108888_Chapter1.pdf"^^ . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . . "S_TE_2108888_Chapter3.pdf"^^ . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . . "S_TE_2108888_Chapter5.pdf"^^ . . . "ANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \r\nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \r\n(PERSERO) UP2D JAWA BARAT (Text)"^^ . . "HTML Summary of #134822 \n\nANALISIS KELAYAKAN PEMUTUS TENAGA (PMT) 20 KV PADA \nPENYULANG RKU DI GARDU INDUK RANCAEKEK PT PLN \n(PERSERO) UP2D JAWA BARAT\n\n" . "text/html" . . . "L Education (General)"@en . . . "T Technology (General)"@en . . . "TK Electrical engineering. Electronics Nuclear engineering"@en . .