ANALISIS KEANDALAN SISTEM DISTRIBUSI 20kV PENYULANG CKNG DI PT. PLN (PERSEO) AREA CIAMIS MENGGUNAKAN ETAP DAN METODE SECTION TECHNIQUE

Faizal Ramadhan Sundara, - (2021) ANALISIS KEANDALAN SISTEM DISTRIBUSI 20kV PENYULANG CKNG DI PT. PLN (PERSEO) AREA CIAMIS MENGGUNAKAN ETAP DAN METODE SECTION TECHNIQUE. S1 thesis, Universitas Pendidikan Indonesia.

[img] Text
S_TE_1704658_Title.pdf

Download (774kB)
[img] Text
S_TE_1704658_Chapter1.pdf

Download (303kB)
[img] Text
S_TE_1704658_Chapter2.pdf
Restricted to Staf Perpustakaan

Download (716kB)
[img] Text
S_TE_1704658_Chapter3.pdf

Download (1MB)
[img] Text
S_TE_1704658_Chapter4.pdf
Restricted to Staf Perpustakaan

Download (367kB)
[img] Text
S_TE_1704658_Chapter5.pdf

Download (286kB)
[img] Text
S_TE_1704658_Appendix.pdf
Restricted to Staf Perpustakaan

Download (705kB)
Official URL: http://repository.upi.edu

Abstract

Keandalan sebuah sistem distribusi adalah indikator yang menyatakan kontinuitas layanan suplai sistem distribusi tenaga listrik ke pengguna. Nilai indikatornya dinyatakan berupa besaran indeks tingkat kegagalan, durasi gangguan dan frekuensi gangguan sistem dalam selang waktu yang ditentukan. Keandalan sistem distribusi 20kV penyulang CKNG di PT. PLN (Persero) Area Ciamis dapat dilihat dari data gangguan listrik yang terjadi, pada tahun 2020 kerap terjadi gangguan listrik dengan penyebab yang berbeda, baik dari gangguan eksternal maupun gangguan internal. Berdasarkan gangguan-gangguan listrik tersebut, maka tujuan dari penelitian ini adalah ingin mengidentifikasi jenis gangguan yang dominan terjadi dan menganalisis besaran nilai keandalan sistem distribusi di wilayah obyek penelitian sehingga untuk tahap perbaikannya dapat dilakukan perbaikan secara efektif dan efisien. Adapun analisis dalam penelitian ini digunakan metode simulasi aplikasi ETAP 19.0.1 dan perhitungan section technique untuk mengetahui indikator gangguan berdasarkan laju kegagalan dan durasi gangguan yang terjadi pada komponen sistem distribusi listrik. Dari hasil penelitian ini diperoleh gambaran bahwa pada penyulang CKNG jenis gangguan yang terjadi lebih dominan oleh adanya akibat hubung singkat fasa ke fasa dan mengakibatkan terjadi gangguan permanen. Penyulang CKNG termasuk tidak handal karena rata-rata frekuensi gangguan listrik yang terjadi dalam selang waktu satu tahun telah melebihi standar frekuensi gangguan yang ditentukan SPLN (59: 1985) dan IEEE (1366-2000), untuk rata-rata durasi gangguan dalam selang waktu satu tahun masih termasuk handal menurut SPLN (59: 1985) dan tidak handal menurut IEEE (1366-2000), dan untuk rata-rata durasi tiap frekuensi gangguan pada masing-masing pelanggan masih termasuk handal menurut SPLN (59: 1985) dan IEEE (1366-2000). Kata Kunci : Keandalan, Sistem Distribusi, ETAP 19.0.1, Metode Section Technique The reliability of a distribution system is an indicator that conveys the continuity of electricity supply services to the user. The value of the indicator is defined as the scale of the failure rate index, the duration of the disorder and the frequency of system disruption within a specified period of time. The reliability of a 20kV distribution system of CKNG feeder PT. PLN (Persero) Area Ciamis can be seen from data of electricity failures, the year 2020 saw several different electrical breakdowns, both from external disruptions and internal disruptions. Based on these electrical disruptions, the aim of the study is to identify the kind of dominant disorder occurring and to analyze the magnitude of the system of distribution in the area of the research object so that repairs can be made effectively and efficiently. As for analysis in study, used a simulation of the application of ETAP 19.0.1 and section technique calculations to know for indicators of interference based on the rate of failure and duration of the interference that occurs in the component of the electrical distribution system. What this study suggests is that an insulation of the dominant type of disorder results from a short phasa to a phasa and causes a permanent breakdown. CKNG feeder are not reliable because the average frequency of electrical interference occurring within a year has exceeded the standard frequency of interference determined by SPLN (59: 1985) and IEEE (1366-2000), for the average duration of one year of interrupts still reliable according to SPLN (59: 1985) and not reliable according to IEEE (1366-2000), and for the average duration of each frequency of interrupts on each customer, it still reliable according to SPLN (59: 1985) and IEEE (1366-2000). Key Words : Reliability, Distribution Systems, ETAP 19.0.1, Section Technique Method

Item Type: Thesis (S1)
Uncontrolled Keywords: Keandalan, Sistem Distribusi, ETAP 19.0.1, Metode Section Technique, Reliability, Distribution Systems, ETAP 19.0.1, Section Technique Method
Subjects: L Education > L Education (General)
T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Fakultas Pendidikan Teknologi dan Kejuruan > Jurusan Pendidikan Teknik Elektro > Program Studi Teknik Tenaga Elektrik
Depositing User: Faizal Ramadhan Sundara
Date Deposited: 04 Oct 2021 04:19
Last Modified: 04 Oct 2021 04:19
URI: http://repository.upi.edu/id/eprint/68110

Actions (login required)

View Item View Item