ANALISIS DAMPAK PEMASANGAN DISTRIBUTED GENERATION PADA SISTEM DISTRIBUSI 20 KV

Ghina Shofi Nur Aisyah, - (2020) ANALISIS DAMPAK PEMASANGAN DISTRIBUTED GENERATION PADA SISTEM DISTRIBUSI 20 KV. S1 thesis, Universitas Pendidikan Indonesia.

[img] Text
S_TE_1600658_Title.pdf

Download (756kB)
[img] Text
S_TE_1600658_Chapter1.pdf

Download (548kB)
[img] Text
S_TE_1600658_Chapter2.pdf
Restricted to Staf Perpustakaan

Download (950kB)
[img] Text
S_TE_1600658_Chapter3.pdf

Download (1MB)
[img] Text
S_TE_1600658_Chapter4.pdf
Restricted to Staf Perpustakaan

Download (765kB)
[img] Text
S_TE_1600658_Chapter5.pdf

Download (431kB)
[img] Text
S_TE_1600658_Appendix.pdf
Restricted to Staf Perpustakaan

Download (4MB)
Official URL: http://repository.upi.edu

Abstract

Penelitian ini bertujuan untuk mengetahui pengaruh pemasangan Distributed Generation (DG) terhadap nilai jatuh tegangan dan rugi-rugi daya nyata pada jaringan distribusi 20 kV penyulang Gunung Dukuh (GNDH). Selain itu penelitian ini juga mempunyai tujuan untuk mengetahui letak pemasangan Distributed Generation (DG) yang optimal untuk mendapatkan nilai jatuh tegangan dan rugi-rugi daya yang paling baik. Latar belakang dilakukannya penelitian ini adalah dikarenakan jatuh tegangan dan rugi-rugi daya merupakan hal yang sering terjadi pada penyulang GNDH di PT. PLN (Persero) area Cimahi. Nilai tegangan pada penyulang GNDH terkadang masih di bawah standar yang telah ditetapkan PLN. Hal itu tentu akan menyebabkan beban tidak bekerja secara optimal bahkan dapat menyebabkan kerusakan pada beban listrik dan pada akhirnya akan sangat merugikan semua pihak, baik pihak konsumen listrik maupun pihak PT. PLN (Persero). Berdasarkan karakteristik DG yang dihubungkan langsung dengan sistem distribusi, maka tidak diperlukan lagi sistem transmisi untuk menyalurkan energi listrik. Hal ini tentunya sangat berpengaruh terhadap penurunan nilai jatuh tegangan dan nilai rugi-rugi daya. Metode yang digunakan dalam penelitian ini adalah simulasi aliran daya menggunakan software ETAP 16.0.0 serta analisis setelah mendapatkan hasil simulasi. Temuan dari penelitian ini yaitu hasil simulasi membuktikan bahwa pemasangan DG mempengaruhi penurunan nilai jatuh tegangan dan rugi-rugi daya pada penyulang GNDH, sebelum pemasangan DG nilai jatuh tegangan pada penyulang GNDH yaitu sebesar 10,1% dan nilai rugi-rugi daya sebelum pemasangan DG yaitu sebesar 446,5 kW. Setelah dilakukan simulasi pemasangan DG didapatkan letak pemasangan dua buah DG yang optimal yaitu pada bus TM 36 dan bus TM 42 dengan menurunnya nilai jatuh tegangan menjadi 1,18% dan nilai rugi-rugi daya menjadi 117,2 kW. This study aims to determine the effect of the installation of Distributed Generation (DG) on the value of voltage drop and real power losses in the distribution network of 20 kV Gunung Dukuh feeder (GNDH). In addition, this study also aims to determine the optimal distribution location of Distributed Generation (DG) to get the best voltage drop and power losses. The background of this research is that the voltage drop and power losses are common in GNDH feeders at PT. PLN (Persero) Cimahi area. The voltage value on the GNDH feeder is sometimes still below the standards set by PLN. This will certainly cause the load not to work optimally and can even cause damage to the electricity load and in the end will be very detrimental to all parties, both the electricity consumer and PT. PLN (Persero). Based on the characteristics of DG directly connected to the distribution system, there is no need for a transmission system to deliver electricity. This is certainly very influential on the decrease in the voltage drop and the value of power losses. The method used in this research is power flow simulation using ETAP 16.0.0 software and analysis after getting simulation results. The findings of this study are the simulation results prove that the installation of DG affects the decrease in voltage drop and power losses in GNDH feeder, before installation of DG the voltage drop in GNDH is 10.1% and the value of power losses before DG installation is amounted to 446.5 kW. After the DG installation simulation, the optimal installation of two DGs is found on the TM 36 bus and the TM 42 bus with a decrease in the voltage drop to 1.18% and a power loss value to 117.2 kW.

Item Type: Thesis (S1)
Additional Information: No Panggil : S TE GIN a-2020; Pembimbing : I. Yadi Mulyadi, II. Habullah; NIM : 1600658
Uncontrolled Keywords: Distributed Generation, Voltage Drop, Power Losses
Subjects: L Education > L Education (General)
T Technology > T Technology (General)
T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Fakultas Pendidikan Teknologi dan Kejuruan > Jurusan Pendidikan Teknik Elektro > Program Studi Teknik Tenaga Elektrik
Depositing User: Ghina Shofi Nur Aisyah
Date Deposited: 27 Apr 2020 04:48
Last Modified: 27 Apr 2020 04:48
URI: http://repository.upi.edu/id/eprint/48543