ANALISIS RUGI DAYA DAN JATUH TEGANGAN PADA JARINGAN DISTRIBUSI 20 KV GARDU INDUK BANDUNG UTARA MENGGUNAKAN METODE FUZZY LOGIC

    Khildan Arif Nurhikam, - and Yadi Mulyadi, - (2025) ANALISIS RUGI DAYA DAN JATUH TEGANGAN PADA JARINGAN DISTRIBUSI 20 KV GARDU INDUK BANDUNG UTARA MENGGUNAKAN METODE FUZZY LOGIC. S1 thesis, Universitas Pendidikan Indonesia.

    Abstract

    Rugi daya adalah hilangnya daya yang diterima oleh konsumen selama proses penyaluran daya dari besar daya yang seharusnya, sedangkan jatuh tegangan adalah hilangnya nilai tegangan saat proses penyaluran teganan dari sisi pengirim kepada penerima. Penelitian ini bertujuan untuk menganalisis rugi daya dan jatuh tegangan pada jaringan distribusi 20 kV Gardu Induk Bandung Utara dengan menggunakan metode fuzzy logic. Latar belakang penelitian ini didasarkan pada kebutuhan akan sistem distribusi tenaga listrik yang efisien dan andal, mengingat kerugian daya dan penurunan tegangan dapat memengaruhi kinerja sistem secara keseluruhan. Metode yang digunakan adalah deskriptif kuantitatif dengan pendekatan perhitungan manual berdasarkan data beban puncak, panjang saluran, jenis kabel, dan impedansi penghantar, yang kemudian dibandingkan dengan hasil simulasi menggunakan metode Sugeno berbasis fuzzy logic melalui MATLAB. Hasil penelitian menunjukkan bahwa rugi daya dan jatuh tegangan terbesar terdapat pada penyulang NLO dengan masing-masing 240.246 Watt (5,3605%) dan 1.471 Volt (7,355%) terjadi saat malam hari tepatnya pada pukul 19.00, sehingga berdasarkan PM ESDM no.20 Tahun 2020 nilai tersebut masih dalam batas toleransi yang ditentukan. Pendekatan fuzzy logic memberikan akurasi yang tinggi sekali dalam memprediksi rugi daya dan jatuh tegangan, dengan nilai MAPE umumnya di bawah 10%, sehingga membuktikan efektivitas metode ini sebagai alternatif dalam pengambilan keputusan teknis untuk peningkatan keandalan distribusi tenaga listrik. Power loss refers to the reduction of electrical power received by consumers compared to the amount that should be delivered, while voltage drop is the loss in voltage that occurs during the transmission process from the sending end to the receiving end. This study aims to analyze power loss and voltage drop in the 20 kV distribution network of the Bandung Utara Substation using the fuzzy logic method. The research is based on the need for an efficient and reliable power distribution system, considering that energy loss and voltage drop can significantly affect overall system performance. A descriptive quantitative method was used, involving manual calculations based on peak load data, conductor length, cable type, and impedance, which were then compared with simulation results using the Sugeno fuzzy logic method implemented in MATLAB. The results show that the highest power loss and voltage drop occurred on the NLO feeder, reaching 240.246 Watts (5.3605%) and 1.471 Volts (7.355%) respectively, during the night peak at 19.00. According to the Ministry of Energy and Mineral Resources Regulation No. 20 of 2020, these values are still within the allowable tolerance limits. The fuzzy logic approach provided a very high level of accuracy in predicting power loss and voltage drop, with MAPE values generally below 10%, demonstrating its effectiveness as a technical decision-making tool to improve the reliability of power distribution systems.

    [thumbnail of S_TE_2107996_Title.pdf] Text
    S_TE_2107996_Title.pdf

    Download (544kB)
    [thumbnail of S_TE_2107996_Chapter1.pdf] Text
    S_TE_2107996_Chapter1.pdf

    Download (259kB)
    [thumbnail of S_TE_2107996_Chapter2.pdf] Text
    S_TE_2107996_Chapter2.pdf
    Restricted to Staf Perpustakaan

    Download (482kB)
    [thumbnail of S_TE_2107996_Chapter3.pdf] Text
    S_TE_2107996_Chapter3.pdf

    Download (731kB)
    [thumbnail of S_TE_2107996_Chapter4.pdf] Text
    S_TE_2107996_Chapter4.pdf
    Restricted to Staf Perpustakaan

    Download (591kB)
    [thumbnail of S_TE_2107996_Chapter5.pdf] Text
    S_TE_2107996_Chapter5.pdf

    Download (253kB)
    [thumbnail of S_TE_2107996_Appendix.pdf] Text
    S_TE_2107996_Appendix.pdf
    Restricted to Staf Perpustakaan

    Download (1MB)
    Official URL: https://repository.upi.edu/
    Item Type: Thesis (S1)
    Additional Information: https://scholar.google.com/citations?view_op=new_profile&hl=id ID SINTA Dosen Pembimbing: Yadi Mulyadi: 6003577
    Uncontrolled Keywords: Kata Kunci : Rugi Daya, Jatuh Tegangan, Fuzzy Logic Sugeno, MATLAB, MAPE. Keywords: Power Loss, Voltage Drop, Sugeno Fuzzy Logic, MATLAB, MAPE.
    Subjects: L Education > L Education (General)
    T Technology > TK Electrical engineering. Electronics Nuclear engineering